MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL

OVERVIEW

CHAPTER 1: INTRODUCTION

Figure 3: Single line diagram

Table 1: MX350 protection functions

GEN

X1
H1

H1

X1

METERING

V, A, W, VAR, VA, PF, HZ

TO LOAD

UTA

UTILITY

(SOURCE-1)

VOLTAGE

CARD

SOURCE

2

POWER

SUPPLY

1

SOURCE

CARD

VOLTAGE

METERING

NEUTRAL

CT CARD

ATS

CONTROLLER

170VDC

RS485

-MODBUS

R

TU

ETHERNET

-MODBUS

TCP/IP

NOTE:1

K

CARD

P

ENGINE

ST

AR

T

CONT

ACT

I/O

CARD

24VDC

TO K CARD

AND

I/O CARD

SUPPLIED BY OTHERS

(3)

CT'S

(1) CT

NOTE:1

TO

SOURCE-2

NOTE:1- FOURTH POLE/NEUTRAL POLE IS AN OPTIONAL FEATURE.

NOTE:1

NOTE:1

27 59 47

25

47

59

27

46

51R

50G 51G

889739A1.CDR

ANSI device

Description

25

Synch check

27

Undervoltage

46

Current balance

47

Voltage phase reversal

50G (option)

Ground instantaneous overcurrent

51G (option)

Ground time overcurrent

51 (option)

Overcurrent

59

Overvoltage