CHAPTER 5: SETPOINTS

SECURITY

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL

5–21

Passcode Level 1, Passcode Level 2, Passcode Level 3

Range: any five-digit number using digits 1 through 5 only or Disabled
Default value: 11111 (level 1), 22222 (level 2)
Access is granted if a passcode has been correctly entered matching the value of this
setpoint.

Access Switch Level

Range: 1, 2, 3
Default value: 1
Sets the access level provided by the access switch being closed. The contact input for
the access switch is configured on the contact inputs page.

Comms security

Range: Enabled, Disabled
Default: Disabled
Sets whether the security feature applies to the communications ports.

NOTE

NOTE:

Setting of the NTD IP Address will not function unless Comms Security is set to Disabled.

Setpoint access

Range: Enabled, Disabled
Default: Enabled
Sets whether the setpoint access is allowed from the control panel display.