User interface specifications, Metering and monitoring specifications, Inputs specifications – GE Industrial Solutions MX350 Instruction manual User Manual

Page 11

Advertising
background image

CHAPTER 1: INTRODUCTION

SPECIFICATIONS

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL

1–7

THD ALARM (CURRENT/VOLTAGE)

Pickup level:...........................................................0.1% to 100.0% in steps of 0.1% (programmable)
Time delay:.............................................................0 to 65535 seconds in steps of 1

OVERCURRENT (PER PHASE/NEUTRAL)

Pickup level:...........................................................0.01 to 2.00 × Nominal Current in steps of 0.01%

(programmable)

Time delay:.............................................................0 to 65535 seconds in steps of 1

User interface specifications

GRAPHICAL CONTROL PANEL

Size: ...........................................................................height 102mm, width 153mm, depth 35mm
LCD: ...........................................................................89 mm (3.5-inch) colour, 320 by 240 pixels
LED indicators: .....................................................7 LEDs
Pushbuttons:.........................................................Alarm Reset, Test, Ctrl, Info, plus 11 LCD screen display

control keys

Ports:.........................................................................USB 2.0 type Mini-B for laptop computer connection

Metering and monitoring specifications

EVENT RECORDER

Capacity: .................................................................256 events
Data storage:........................................................non-volatile memory

FREQUENCY METERING

Range: ......................................................................40.00 to 70.00 Hz in steps of 0.01
Accuracy:................................................................±0.05 Hz

POWER METERING

Real power range: ..............................................–2000.0 to 2000.0 kW in steps of 0.1
Apparent power range:....................................0.0 to 2500.0 kVA in steps of 0.1
Accuracy:................................................................±2.0% of full scale with 5 A CT

POWER FACTOR METERING

Range: ......................................................................–0.99 to +0.99 in steps of 0.01
Accuracy:................................................................±0.05

Inputs specifications

CONTROL VOLTAGE INPUT

Input range:...........................................................60 V to 300 V AC
Nominal frequency: ...........................................50 or 60 Hz

DIGITAL INPUTS

Nominal input voltage:.....................................24 V DC
Recognition time:................................................2 cycles
Continuous current draw:...............................4 mA
Type:..........................................................................opto-isolated inputs
External switch: ...................................................wet contact

CALCULATION METHOD
( [I

M

- I

AV

] / I

AV

) x 100%

Where:
I

AV

= average phase current

I

M

= current in a phase with maximum deviation from I

AV

Advertising