5–2

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL

UNDERSTANDING SETPOINTS

CHAPTER 5: SETPOINTS

Figure 1: Setpoints home page

The soft-keys on the Home > Setpoints page open pages two levels down, since the pages
immediately below this page are blank. For example, the Config soft-key opens the Home
> Setpoints > Config > ATS
page.
The pages containing setpoint fields, except for the inputs and outputs pages, are in a
common format. This is a simple tabular format with two columns: setpoint name and
units, and setpoint value. Setpoints for features that are not enabled are omitted from the
page.

CAUTION

CAUTION:

Setpoints may be changed while the ATS is in operation; however it is not
recommended to change parameters while the ATS load is fed from Source 2.

Setpoints will remain stored indefinitely in the internal non-volatile memory even when
control power to the is removed. Protection parameters are based on the entered data.
This data must be complete and accurate for the given system for reliable protection and
operation of the ATS.

Setpoint text abbreviations

The following abbreviations are used in the setpoints pages.

A, Amps: amperes

AUX: auxiliary

COM, Comms: communications

CT: current transformer

GND: ground

Hz: Hertz

MAX: maximum

MIN: minimum

SEC, s: seconds

UV & U/V: undervoltage

VT: voltage transformer

Ctrl: control

Hr & hr: hour

UTC: co-ordinated universal time

ops: operations