Numeric setpoints – GE Industrial Solutions MX350 Instruction manual User Manual

Page 44

Advertising
background image

3–14

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL

GRAPHICAL CONTROL PANEL

CHAPTER 3: INTERFACING WITH THE MX350 AT CONTROLLER

Figure 20: Enumeration setpoint editing

Numeric setpoints

Numeric setpoints accept a numerical value within a specific range. The numeric setpoint
editor is a numeric input panel, with the current value shown on the number display. The
minimum, maximum, step, and default values are shown on the left of the keypad, and the
label of the setpoint being edited is displayed on the menu bar of the setpoint editor.

Figure 21: Numeric setpoint editor window

The navigational soft keys change the numeric key in focus, which is highlighted in orange.
There are also five functional soft-buttons in the popup window.

BkSpc: This key performs the backspace function, clearing the last digit or decimal
from the display.

CLR: This key clears the field’s value from the display

Default: This key returns the setpoint value to its default value.

OFF: This key disables the setpoint and is visible only for setpoints that can be
disabled.

In order to activate the functions offered by these buttons, the user has to highlight the
appropriate button and press "Select".
The UP and DOWN front panel keys can also be used to increment and decrement the
setpoint by its step value. Clicking the ENTER key verifies the displayed value. If the
setpoint value is valid, it is stored as the new setpoint value and the editor is closed.
Otherwise, an error statement is displayed and the Default soft-button is brought to focus.
Clicking HOME before the value is stored cancels the edit sequence and recalls the home
page.
The following procedure describes how to edit a numeric setting.
1.

Use the navigation keys to select the relevant setting page.

2.

Use the navigation keys to select the relevant setting field.

Advertising