Communications specifications, Testing and certification – GE Industrial Solutions MX350 Instruction manual User Manual

Page 13

Advertising
background image

CHAPTER 1: INTRODUCTION

SPECIFICATIONS

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL

1–9

Communications specifications

ETHERNET (COPPER)

Modes:......................................................................10/100 MB (auto-detect)
Connector:..............................................................RJ-45
SNTP clock synchronization error: ..............<200 ms (typical)
Protocol: ..................................................................Modbus TCP

RS485 PORT

Port: ...........................................................................opto-isolated
Baud rates:.............................................................up to 115 kbps
Protocol: ..................................................................Modbus RTU, half-duplex
Maximum distance: ...........................................1200 m
Isolation:..................................................................2 kV

USB PORT

Standard specification:....................................Compliant with both USB 2.0 and USB 1.1
Data transfer rate:..............................................USB device emulating serial communications port at

115 kbps

Connector:..............................................................USB2.0 Mini-B

Testing and certification

TESTING AND CERTIFICATION

Test

Reference Standard

Test Level

Dielectric Voltage Withstand:

EN60255-5

2.0 KV

Impulse Voltage Withstand:

EN60255-5

5 KV

Insulation Resistance:

EN60255-5

500 V DC > 100 Mohm

Damped Oscillatory:

IEC61000-4-18/IEC60255-22-1

2.5 KV CM, 1 KV DM

Electrostatic Discharge:

EN61000-4-2/IEC60255-22-2

Level 4

RF Immunity:

EN61000-4-3/IEC60255-22-3

Level 3

Fast Transient Disturbance:

EN61000-4-4/IEC60255-22-4

Level 4

Surge Immunity:

EN61000-4-5/IEC60255-22-5

Level 3 & 4

Conducted RF Immunity:

EN61000-4-6/IEC60255-22-6

Level 3

Power magnetic Immunity:

IEC61000-4-8

Level 4

Voltage Dip & Interruption:

IEC61000-4-11

0,40,70% dips 250/300cycle

interrupts

Radiated & Conducted Emissions: CISPR11 /CISPR22/ IEC60255-25

Class A

Ingress Protection:

IEC60529

IP20 (base unit) IP54 (Control

Panel)

Environmental (Cold):

IEC60068-2-1

-20

o

C 16 hrs

Environmental (Dry heat):

IEC60068-2-2

85

o

C 16hrs

Relative Humidity Cyclic:

IEC60068-2-30

6-day variant 2

Fast Transient Disturbance:

IEEE C37.90.1

4 KV CM & DM

SWC Damped Oscillatory:

IEEE C37.90.1

2.5 KV CM

Electrostatic Discharge:

IEEE C37.90.3

8 KV CD, 15 KV AD

Advertising