MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL

FLEXLOGIC™ OVERVIEW

CHAPTER 8: FLEXLOGIC™

The operators available in FlexLogic™ are shown below.

Table 1: FlexLogic™ operators

The FlexLogic™ operands available in the MX350 are listed below.
Control operands: auto/manual
Access Switch Closed..............................Asserted when the corresponding Access Switch input is active.
Load Control 1.............................................Asserted when the Load Control 1 output is active.
Load Control 2.............................................Asserted when the Load Control 2 output is active.
Load Control 3.............................................Asserted when the Load Control 3 output is active.
Load Control 4.............................................Asserted when the Load Control 4 output is active.
Load Control 5.............................................Asserted when the Load Control 5 output is active.
Load Control 6.............................................Asserted when the Load Control 6 output is active.
Remote Timer Bypass.............................Asserted when one or more of the corresponding Bypass Xfer

Time Delay to S1 or Bypass Xfer Time Delay to S2 inputs are
active, or when either one or both of the equivalent
communications signals has been received.

Any Alarm
Bypass ATS on S1.......................................Asserted when the corresponding AB4 input is active.
Bypass ATS on S2.......................................Asserted when the corresponding AB3 input is active.
Process Interlock A Alarm......................Asserted when customer configurable interlock A is active.
Process Interlock B Alarm......................Asserted when customer configurable interlock B is active.
Process Interlock C Alarm......................Asserted when customer configurable interlock C is active.
Process Interlock D Alarm .....................Asserted when customer configurable interlock D is active.
Process Interlock E Alarm......................Asserted when customer configurable interlock E is active.

Operator

Inputs

Description

<operand>

none

The output value is the value of the named <operand>.

NOT

1

The output value is “on” if and only if the intput value is “off”.

OR

2 to 16

The output value is “on” if and only if any of the input values are

“on”.

AND

2 to 16

The output value is “on” if and only if all of the input values are

“on”.

NOR

2 to 16

The output value is “on” if and only if all of the input values are

“off”.

NAND

2 to 16

The output value is “on” if and only if any of the inputs values are

“off”.

XOR

2

The output value is “on” if and only if one input value is “on” and

the other input value is “off”.

TIMER

1

The output value is “on” if the input value has been “on” for the set

pickup time. Once the output value is “on”, it remains “on” until the

input value has been “off” for the set dropout time.

LATCH

2

The output value is the state of a reset-dominant volatile bi-stable

latch, where the first input value is the set input, and the second

input value is the reset input.

Positive one-shot

1

The output value is “on” for one processing cycle following an off-

to-on transition of the input value.

Negative one-shot

1

The output value is “on” for one processing cycle following an on-

to-off transition of the input value.

Dual one-shot

1

The output value is “on” for one processing cycle following either

an on-to-off or off-to-on transition of the input value.

ASSIGN <operand>

1

The input value is assigned to the named operand. There is

otherwise no output value.

END

none

The first END encountered terminates the current processing

cycle.