Dielectric strength testing, Dielectric strength testing - 14 – GE Industrial Solutions MX350 Instruction manual User Manual

Page 30

Advertising
background image

2–14

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL

ELECTRICAL INSTALLATION

CHAPTER 2: INSTALLATION

Dielectric strength testing

Figure 16: Testing for dielectric strength

It may be required to test for dielectric strength (“flash” or “HI-POT”) with the MX350
installed. The MX350 is rated for 1.9 kV AC for 1 second, or 1.6 kV AC for 1 minute (per UL
508) isolation between relay contacts, CT inputs, VT inputs and the surge ground terminal
SG. Some precautions are required to prevent damage to the MX350during these tests.
Filter networks and transient protection clamps are used between VT input and the surge
ground terminal. This is intended to filter out high voltage transients, radio frequency
interference (RFI), and electromagnetic interference (EMI). The filter capacitors and
transient suppressors may be damaged by continuous high voltage. Disconnect the surge
ground terminals (C8 and D8) during testing of VT inputs. The CT inputs, control power, and
output relays do not require any special precautions. Low voltage inputs (less than
30 volts), and RS485 communication ports are not to be tested for dielectric strength under
any circumstance (see above).

Do not HI-POT test

HI-POT test at 1.9 kV AC for 1 second, or
1.6 kV AC for 1 minute (per UL 508)

LINE FAULT

ON

POWER

FAULT RESET

kV

VOLTAGE ADJUST

HV ON

DIELECTRIC STRENGTH TESTER

BLACK RED

Remove surge ground during test

*

CPU module

C8

C7

C6

C5

C4

C3

C2

C1

S

u

rg

e

G

round

D1
D2
D3
D4
D5
D6
D7
D8

CT
Mod

u

le

CT1

CT2

CT3

CT4

Power

supply

L

N

G

Automatic Transfer Control System

VT1 module

VT

1

VT

3

RS485

Thermistor

VT

2

Cor

e

balance

S

u

rg

e

G

round

889738A1.CDR

+ – C + – R I SG

* *

* * *

D8

D7

D6

D4

D3

D2

D1

S

u

rg

e

G

round

D5

VT

1

VT

3

VT

2

VT2 module

* *

* * *

Advertising