Physical specifications, Environmental specifications – GE Industrial Solutions MX350 Instruction manual User Manual

Page 14

Advertising
background image

1–10

MX350 AUTOMATIC TRANSFER CONTROL SYSTEM – INSTRUCTION MANUAL

SPECIFICATIONS

CHAPTER 1: INTRODUCTION

Physical specifications

DIMENSIONS

Size: ...........................................................................Base: 62 mm [2.44"] (W) × 90 mm [3.54"] (H) × 113 mm [4.45"]

(D) (+ terminals 10mm [0.39"])
Expansion: 62 mm [2.44"] (W) × 90 mm [3.54"] (H) × 113 mm
[4.45"] (D)
GCP: 153 mm [6.02"] (W) × 102 mm [4.02"] (H) × 35 mm [1.38"]
(D)

Weight (Base):.......................................................0.75 kg [1.65 lb]

Environmental specifications

APPROVALS

Applicable Council Directive

According to

CE compliance:

Low voltage directive

EN60255-5, EN60947-1, EN60947-6-1

EMC Directive

EN61000-6-2/ EN61000-6-4

ISO:

Manufactured under a registered

quality program

ISO9001

ENVIRONMENTAL SPECIFICATIONS

Ambient temperatures:
Storage/shipping:

- 40

o

C to 90

o

C *

Operating:

-20

o

C to 60

o

C * (Base Unit and Basic Control Panel)

-20

o

C to 50

o

C * (Graphical Control Panel)

* 1" around Base Unit

Humidity:

Operating up to 95% (non condensing) @ 55

o

C (As

per IEC60068-2-30 Variant 2, 6days)

Altitude:

2000 m (max)

Overvoltage Category:

II

Ingress Protection:

IP20 (Base Unit), IP54 (Control Panel)

Advertising