Features

Output Current “Walk-in”

This circuit controls the time (up to eight seconds) required for the rectifier to

reach normal operating conditions after it is turned on. This feature minimizes

the starting surge on the customer's power source.

Output Protection

Rectifier is equipped with an internal fuse for plant protection if a fault occurs

in a rectifier.

Electronic Current Limit

When the output current tends to increase above the current limit set point,

the current limit circuit overrides the voltage regulating signal and safely limits

the output current of the rectifier, thus preventing damage to itself or the

load.

High Voltage Shutdown (HVSD)

The rectifier senses the voltage at its output terminals. If this voltage is too

high, the rectifier will shut down to prevent the high voltage from damaging

itself or the load.

Restart

Upon shutdown, the rectifier will attempt to restart. The rectifier will also

accept a restart command from the controller for a remote restart. The

rectifier will attempt to restart three times before issuing a rectifier fail alarm

to the controller.

Fan Alarm and Control

The rectifier contains a cooling fan. The fan’s speed, which is based on

ambient temperature and output power level, is lowered during low-load and

low-temperature conditions to minimize audible noise and maximize fan life.