Serial (pc) port, Alarm buzzer, Contrast adjust – GE Industrial Solutions GPS2436 User Manual
Page 54
Galaxy Power System GPS2436
Issue 1 August 2012
54
measures this voltage to regulate the system bus voltage as well as display it as the
battery plant bus voltage. The value of this voltage is used for many other controller
related features.
Serial (PC) Port
A ground referenced RS-232 local port is provided at the front of the display to allow
easy connection to a personal computer or terminal using ANSI T1.317 object oriented
command language.
Lineage Power’s
EasyView is also available to provide a user friendly
system interface locally or remotely. See figure 4-6.
Alarm Buzzer
The audible alarm buzzer is located on the front panel display assembly. It can be
programmed from the front panel display to operate as follows:
• Disabled for ALL Alarms
• Audible on PCR
• Audible on PMJ
• Audible on PMN
Contrast Adjust
• For L50, L52 Displays:
Press the + or – keys and hold until the display changes it’s contrast
setting. Once the desired setting is reached, release the button.
• For L51 Displays:
Using a small flat head jeweler’s screwdriver, insert it into the small
opening at the top of the display assembly (above the UP arrow). Turn
clockwise or counter clockwise until the display contrast is set.