Galaxy Power System GPS2436

Issue 1 August 2012

90

13 Safety

Please read and follow all safety instructions and warnings before servicing the GPS2436.

Reference the GPS Installation Guide for safety statements specific to the modules.

Safety Statements

Please read and follow all safety instructions and warnings before installing,

maintaining, or repairing the system:

The CE Mark demonstrates compliance with the European Union Council

Directives for Low Voltage and EMC.

The UACD is Underwriters Laboratories (UL) recognized per Subject Letter 1801,

DC Power Distribution Centers for Telecommunications Equipment.

Install only in restricted access areas (dedicated equipment rooms, equipment

closets, or the like) in accordance with articles 110-26, 110-27, and 110-18 of the

U.S. National Electric Code (NEC-2011), ANSI/NFPA No. 70, and pursuant to

applicable local codes.

This equipment is to be used in controlled environments (an area where the

humidity is maintained at levels that cannot cause condensation on the

equipment, the contaminating dust is controlled, and the steady-state ambient

temperature is within the range specified).

This equipment has been evaluated for continuous use in ambient temperature

from 5°C to 55°C.

This equipment must not be installed over combustible surfaces.

For installations in the United States, Listed compression connectors are to be

used to terminate Listed field-wired conductors where required. For all

installations, the appropriate connector is to be applied only to the correct size

conductor as specified by the connector manufacturer, using only the connector

manufacturer’s recommended tooling or tooling approved for that connector.

The shelf in combination with the EP300048ATEZ has not been evaluated for hot-

swapping.

If the proper connector for the country of installation is not provided, obtain

appropriate connectors and follow manufacturers and all local requirements for

proper connections. All national and local rules and regulations should be

followed when making field connections.