Issue 1 August 2012

79

3. The rectifier’s current output must be unbalanced by more than

10% from the average output currents of the other rectifiers.

Because item 3 is difficult to achieve in a simulation test of properly

functioning serial rectifiers, (even with load share disabled), rectifiers

are tested one at a time, rather than as a group. Slightly different test

procedures are used for special applications in batteryless plants. Serial

rectifiers have their own internal restart circuits which will function 3

times before the rectifier locks itself out and initiates a High Output

Rectifier Fail Alarm to the controller. If there is a sufficient interval

between restart and a subsequent shutdown the rectifier resets its

restart counter. The controller initiates a restart signal a few seconds

after the

first RFA (HO) alarm is received. After the second RFA (HO) is received,

the controller waits 5 minutes before sending one additional restart

signal.

1.

Verify the Auto Restart is enabled from the front panel menus:

2.

Turn off all rectifiers except the rectifier under test by operating their

power switches to STBY.

3.

Adjust the dummy load to provide 10 to 30% of the rectifier’s output

capacity.

4.

Using the Voltage Alarms Menu Screens, note High Voltage Alarm

threshold value. _________

5.

Using the Float Settings Menu Screens, select Set Point and note the

value. ________

NOTE:

The next step WILL RAISE the system voltage.

6.

Use the Arrows, and UP/DOWN keys to change the system float voltage

setpoint to 0.1V above the High Voltage Alarm Threshold.. Press ENTER

to save.

7.

Controller Observations:

• The plant voltage increases

• Power Major alarm (PMJ) is generated

• RECT and MAJ LEDs are illuminated

Rectifier Observations:

• When the voltage increases to the HV (FLOAT) level the

rectifier shuts down.

• The Green ON LED on the rectifier blinks, the ALM LED on

the rectifier is not lit.

• After 5-6 seconds the rectifier initiates its own restart