Galaxy Power System GPS2436

Issue 1 August 2012

68

Format

This field allows you to select one of the

following time display formats: 12 or 24 hour.

Use the <+> or <-> key to select the desired

format and press <ENTER> to save the

change.

Time

Allows you to change/set the time.

Daylight

Enables or Disables Daylight Savings.

3.

SYSTEM SHUNT

Type

This selection allows the operator to

configure the type of shunt that is connected

to the controller. Possible values are LOAD,

BATTERY, or NONE. The configuration is

determined by the plant architecture. Refer

to the GPS Power Plant Product Manual for a

description of these architectures.

In a plant using distributed architecture a

shunt type of NONE should be selected. In

this arrangement, up to 32 shunts, located

between batteries and plant bus bars, can be

connected to the Bay Interface Cards in the

system bays. The controller reads the shunt

currents over the serial data connection. The

load current displayed is derived from the

total of battery currents and the total of

rectifier currents.

In a plant using centralized architecture,

either LOAD or BATTERY should be selected.

A maximum of two shunts of the same

amperage can be connected through P6 on

the BSH. A shunt type of LOAD means that a

load shunt, located between load and plant

bus bars, is connected. The load current

displayed on the front panel is the sum of the

two shunt currents. A shunt type of BATTERY

means that a battery shunt located between

the batteries and plant bus bars is connected.

The load current displayed on the front panel

is derived from the total battery current and