GE Industrial Solutions GPS2436 User Manual

Page 86

Advertising
background image

Galaxy Power System GPS2436

Issue 1 August 2012

86

Galaxy Power System 2436 Specifications (continued)

Mechanical

Cabinet

Full Height

Nominal Cabinet Dimensions
(H x W x D)

2100 H x 600 W x 600 D mm
(82.6 H x 23.6 W x 23.6 D in.)

Units Per Initial Cabinet

Full Height

Rectifiers

1 -

36

Controller

1

Battery Disconnect Modules

0 - 1

DC Distribution

Maximum discharge is 1600 amps per cabinet. No distribution panels can be
installed in a rectifier only cabinet, as many distribution panels as will fit can be
installed in other cabinets.

Units Per Supplemental Cabinet

Rectifiers

1 -

36

Battery Disconnect Modules

0 - 1

DC Distribution

Maximum discharge is 1600 amps per cabinet. No distribution panels can be
installed in a rectifier only cabinet, as many distribution panels as will fit can be
installed in other cabinets.

Environmental

Operating Ambient
Temperature

NE100AC24ATEZ



-40°C to +75°C

Altitude

-50 to 4000 meters
Note: For altitudes between 1500 and 4000 meters, derate the maximum
temperature by 0.656°C per 100 meters.

Humidity

5% to 95% non-condensing

Radiated and Conducted
Emissions

EN50082-1, EN50082-2, EN50081, EN61000

Electromagnetic Immunity

Level B

Earthquake Rating

Zone 4, upper floors

Standards Compliance

Agency Approvals

CE Marked, UL
Underwriters Laboratories (UL) Listed per Subject Letter 1801, DC Power
Distribution Centers for Telecommunications Equipment