GE Industrial Solutions GPS2436 User Manual

Page 59

Advertising
background image

Galaxy Power System GPS2436

Issue 1 August 2012

59

Symbol

Default Designation

Default

Severity

Default LED Default Relay

HCL

History Cleared

RO

None

None

HFV

High Float Voltage

Minor

RECT

None

HVA

High Voltage

Major

RECT

HV

LMR

Limited Recharge

Minor

RECT

None

LVD

Low Voltage Disconnect

Minor

BAT

None

LVDA

Low Voltage Disconnect Fail

Minor

BAT

None

MCM

Major Communication Fail

Minor

CTLR

None

MDF

Module Failure

Minor

RM

None

MOR

Measurement Out Of Range

Minor

RM

None

MTC

Module Type Conflict

Warning

None

None

NNC

Number Not Configured

Warning

None

None

OSA

Open String

Minor

BAT

None

PFD

Password At Default

Warning

None

None

PGI

Program Line Invalid

Major

None

None

PHT

Processor Halt

RO

None

None

POR

Number Did Not Respond

Warning

None

None

RLS1

Redundancy Loss

Ninor

RECT

None

RPI

Rectifier/Plant Inconsistency

Warning

None

None

RTL

Reserve Time Low

Minor

BAT

None

SNC

Shunt Not Configured

Warning

None

None

STF

Self Test Failed

Minor

CTLR

CTLR

TPA

Thermal Probe Failure

Minor

CTLR

CTLR

URC

User Relay Conflict

Warning

None

None

VLA

Very Low Voltage

Critical

BAT

UR3

VSF

Sense/Control Fuse

Major

CTLR

CTLR

ZID

ID Not Configured

Major

RECT

None

Advertising