Symbol
Default Designation
Default
Severity
Default LED Default Relay
HCL
History Cleared
RO
None
None
HFV
High Float Voltage
Minor
RECT
None
HVA
High Voltage
Major
RECT
HV
LMR
Limited Recharge
Minor
RECT
None
LVD
Low Voltage Disconnect
Minor
BAT
None
LVDA
Low Voltage Disconnect Fail
Minor
BAT
None
MCM
Major Communication Fail
Minor
CTLR
None
MDF
Module Failure
Minor
RM
None
MOR
Measurement Out Of Range
Minor
RM
None
MTC
Module Type Conflict
Warning
None
None
NNC
Number Not Configured
Warning
None
None
OSA
Open String
Minor
BAT
None
PFD
Password At Default
Warning
None
None
PGI
Program Line Invalid
Major
None
None
PHT
Processor Halt
RO
None
None
POR
Number Did Not Respond
Warning
None
None
RLS1
Redundancy Loss
Ninor
RECT
None
RPI
Rectifier/Plant Inconsistency
Warning
None
None
RTL
Reserve Time Low
Minor
BAT
None
SNC
Shunt Not Configured
Warning
None
None
STF
Self Test Failed
Minor
CTLR
CTLR
TPA
Thermal Probe Failure
Minor
CTLR
CTLR
URC
User Relay Conflict
Warning
None
None
VLA
Very Low Voltage
Critical
BAT
UR3
VSF
Sense/Control Fuse
Major
CTLR
CTLR
ZID
ID Not Configured
Major
RECT
None