change.

6.

Batteries

Model

The configuration of this field selects the

installed battery type from a list of pre-

defined battery types used in reserve time

prediction and enhanced battery test

features. Move the cursor to the field and

use the <+> or <-> key to adjust the threshold

value. Press <ENTER> to save the change.

Strings

The configuration of this field selects the

number of battery strings in the system. This

parameter is used in reserve time prediction

and enhanced battery test features. Move

the cursor to the field and use the <+> or <->

key to adjust the threshold value. Press

<ENTER> to save the change.

Cells/String

The configuration of this field selects the

number of installed cells in the battery

strings. This parameter is used in reserve

time prediction and enhanced battery test

features. Move the cursor to the field and

use the <+> or <-> key to adjust the threshold

value. Press <ENTER> to save the change.

Type

The configuration of this field selects the

batter type, Flooded or Valve Regulated

(sealed). This parameter is used in reserve

time prediction and enhanced battery test

features. Move the cursor to the field and

use the <+> or <-> key to adjust the threshold

value. Press <ENTER> to save the change.

7.

Thermal Comp

This feature allows dynamic control of sealed

cell battery voltage as a function of

temperature.

Enabled

Enables or Disables the Thermal

Advertising