Data switch card, Alarm termination board – GE Industrial Solutions GPS2436 User Manual

Page 41

Advertising
background image

Galaxy Power System GPS2436

Issue 1 August 2012

41

Data Switch Card

Step

Action

NOTE:

Installation or replacement of this pack can be done “hot”; power removal

is not necessary.

2.

Install two 407882133 standoffs on the BSJ intelligent board. Screw threads

are protruding just below TB1, located at the upper left hand corner of the

MCR1 board.

3.

Place BSW pack inside the 847950938 insulator.

4.

Plug BSW pack into the P205 connector on the BSJ intelligent controller

board

5.

Secure the BSW board to the standoffs with two 900562208 screws.

NOTE:

To install the Data Switch Extension board, please see the User’s Guide for

Millennium II Controller Advanced Features manual.

Alarm Termination Board
Alarm Termination board options provide for wire wrapped or insulation displacement

(punch down) terminations. The Alarm Termination Board for a specific application may

require field installation. To do so, perform the following steps:

Step

Action

1.

In the upper right hand corner of the MCR1 board, find the alarm board

already installed.

2.

Remove the two screws holding the board at the top.

3.

Holding the board on both sides, slowly, but firmly, remove the alarm board

from the P8 connector.

4.

Unpack the new board from its box, carefully observing proper ESD

procedures.

5.

Connect the alarm board to P8 and press down firmly, until the board is

seated.

6.

Secure the alarm board at the top using the two screws removed earlier.