Table 9-H: Enhanced Remote Security Features

The modem and auxiliary ports can be configured for full access and read-only using DIP

switch 202-7. Restricted access is also available. This prevents changes ia the modem

and auxiliary ports that will affect the state of the plant, even when logged in as a Super-

User or Administrator. This enhanced remote security is enabled and disabled with DIP

switch SW202-6. The functions and parameters restricted with the enhanced remote

security feature are listed in this table.

Enable or disable Rectifier Restart feature

Change All Rectifier On Threshold

Change Timed Manual Boost Duration

Change Boost Current Threshold

Change Rectifier Status to “Standby”/ “Vacant” status is prohibited. The change to

“On”status is allowed.

Change Rectifier Shunt Voltage configuration

Change Rectifier Float High Voltage Shutdown Threshold

Change Rectifier Boost High Voltage Shutdown Threshold

Change Rectifier Float Set Point

Change Rectifier Boost Set Point

Change Rectifier Boost Current Limit

Change Converter Voltage Set-Point

Change Converter Low Voltage Disconnect Threshold

Change Converter Low Voltage Reconnect Threshold

Enable or disable Converter Low Voltage Disconnect feature

Change Converter Status to “Standby”/ “Vacant” status is prohibited. The change to

“On”status is allowed.

Change Battery High Temperature Threshold

Enable or disable Battery Current Limit

Change Battery Limit Threshold

Change Battery Contactor Status to “Open” status is prohibited. The change to “Close”

status is allowed.

Change Battery Disconnect Threshold

Change Battery Reconnect Threshold

Change Very Low Voltage Alarm Threshold and Severity

Change Multiple Rectifier Fail Alarm Threshold and Severity

Change Limited Recharge Current Alarm Threshold and Severity

Change Excess Rectifier Drain Alarm Threshold and Severity

Change Engine Transfer Timeout Alarm Threshold and Severity

Change Reserve Time Low Alarm Threshold and Severity

Change Multiple Converter Fail Alarm Threshold and Severity

Change Battery On Discharge Alarm Threshold and Severity