Local port, Software, Wiring alarm outputs – GE Industrial Solutions GPS2436 User Manual

Page 45

Advertising
background image

Galaxy Power System GPS2436

Issue 1 August 2012

45

Local Port

Software

EasyView software is a Windows-compatible communications package designed specifically for

use with Galaxy controllers. Download EasyView software from http://www.lineagepower.com

Wiring Alarm Outputs

These external alarms may be wired to customer external office alarms at their

destination.

Form-C Alarm Contact Ratings

60Vdc, 0.3A

Conductor Size for terminating on Alarm

board

18 – 22AWG (if less than 18AWG, use

multi-conductor cable for mechanical

integrity)

Refer to Table 9-B and 9-C for lead designations and their descriptions for leads

terminating on the BSL alarm interface board.

Table 9-B: Controller Alarm Descriptions and Pin Numbers

Pin

Number

Signal Name

Pin

Number

Signal Name

Pin

Number

Signal Name

1

PCRAO

33

MJFR

65

FAN

2

PCRAC

34

MNFR

66

AMN

3

PCRAR

35

MNFC

67

TFLT

4

PCRVR

36

MNFO

68

TBST

5

PCRVC

37

BDO

69

TRTN

6

PCRVO

38

BDC

70

PBTR

7

PCREO

39

BDR

71

PBT

8

PCREC

40

ACFR

72

OS

9

PCRER

41

ACFC

73

TR1

10

PMJAR

42

ACFO

74

TEQ

11

PMJAC

43

RFAO

75

ETR

12

PMJAO

44

RFAC

76

ETRR

13

PMJEO

45

RFAR

77

RO

14

PMJEC

46

HVR

78

ROR

15

PMJER

47

HVC

79

TR2

16

PMJVR

48

HVO

80

TR4

17

PMJVC

49

UR1O

81

RBRPO

Advertising