Compensation Feature. Move the cursor to

the field and use the <+> or <-> key to Enable

or Disable. Press <ENTER> to save the

change.

High Temp

Comp

This feature allows the system to

compensate for high temperatures.

Volt Step

Down

Battery step temperature can be set from

113-185F. At this temperature, the system

voltage is reduced by 0.17 X # of cells/string.

High Comp

Limit

This sets the maximum temperature for

which thermal compensation is active.

Decrease

This sets the slope (mV/degC) for high

temperature compensation.

Nominal

Temp

This field set the temperature at which no

compensation is required. The system

voltage is at the setpoint float mode.

Low Temp Comp

This feature allows the system to

compensate for low temperatures.

Low T Comp This enables or disables the low temperature

compensation feature.

Low Comp

Limit

This sets the minimum temperature for

which thermal compensation is active.

Increase

This sets the slope (mV/degC) for low

temperature compensation.

8.

Recharge Current

Limit

This feature sets the total amount of current

that will be allowed to recharge the batteries.

Limit

The configuration of this field enables or

disables the feature.

Limit to

This programmable value sets the maximum

amount of recharge current (in Amps) that

will be allowed for recharging the batteries.

The range is from 10 – 1000A.

9.

Contactors

Up to three optional LVD devices can be

connected to a Millennium and configured

from this screen.