5 AC Input Panels

Overview

AC Service

The ac input panel provides the facility to terminate 3-phase ac service to the GPS2436 system

or to distribute individual 1-phase ac supplies to each of the system rectifier positions.

Depending upon the option ordered, the panel will connect 3-wire (three phases), 4-wire (three

phases + neutral), or individual 2-wire (single phase, either 2 hot leads or 1 hot lead and neutral)

input ac service.

Some options provide circuit breakers to protect the conductors providing ac service to the

individual rectifiers. Other systems contain a terminal strip and the conductors are protected by

circuit breakers located in the building’s ac service panel.

Note: All wire sizes based on the US National Electric Code.

Figure 6-1: AC Input Terminal strip Panel

Figure 5-2: AC block.

Factory wiring from AC block to rectifier shelf shown.