High voltage shutdown – new installations only – GE Industrial Solutions GPS2436 User Manual

Page 78

Advertising
background image

Galaxy Power System GPS2436

Issue 1 August 2012

78

5.

Using the Float Settings Menu Screens, select Set Point.

6.

Use the Arrows, and UP/DOWN keys to change the system float voltage

setpoint to it’s original value. Press ENTER to save.

7.

Observe:

• The plant voltage decreases to the original set voltage

• Power Minor alarm (PMN) retires

• RECT and MIN LEDs are extinguished

High Float Voltage Alarm – Systems with Actual Loads

Step

Action for Testing the High Float Voltage Alarm

NOTE:

Clear all controller alarms for this test.

NOTE:

The System Voltage WILL NOT change.

NOTE:

The high float voltage alarm test is completed by changing the threshold

for this condition below the system voltage to make it active.

1.

Using the Float Settings Menu Screens, select Set Point and note the

value. ________

2.

Using the Voltage Alarms Menu Screens, note the High Float Alarm

threshold value. _________

3.

Use the Arrows, and UP/DOWN keys to change the High Float Alarm

Threshold to 0.1V below the System Voltage. Press ENTER to save.

4.

Observe:

• Power Minor alarm (PMN) is generated

• RECT and MIN LEDs are illuminated

5.

Using the Voltage Alarms Menu Screens, change the High Float Alarm

threshold value to it’s original value. Press ENTER to save.

6.

Observe:

• Power Minor alarm (PMN) retires

• RECT and MIN LEDs are extinguished

High Voltage Shutdown – New Installations Only

STEP

Action for Testing High Voltage Shutdown Alarm

NOTE:

The High Voltage Shutdown Test is recommended only for new

installations where a dummy load is available prior to the application of

office load, and batteries are connected.

NOTE:

There are three requirements for a serial rectifier to shut down upon a

controller initiated High Voltage Alarm.

1. The plant voltage must be above the level set for the High

Voltage alarm at the VOLTAGE ALARMS menu screen:

MENUCONFIGUREFLOAT SETTINGSVOLTAGE ALARMS

2. The rectifier must be delivering a current of at least 10% of its

capacity.

Advertising