Default display – GE Industrial Solutions GPS2436 User Manual

Page 60

Advertising
background image

Galaxy Power System GPS2436

Issue 1 August 2012

60

Table 9-K: Rectifier Alarm Defaults

Symbol

Default Designation

Default

Severity

Default LED Default Relay

ACF

AC Fail

Minor

AC

ACF

CLM

Rectifier Current Limit

RO

None

None

ERD

Excess Rectifier Drain

Minor

RECT

None

ETS

External Transfer Shutdown

Minor

RECT

None

HPA

Half Power

Minor

RECT

None

LCA

Low Current Alarm

Minor

RECT

None

LSF

Load Share Fuse

Minor

RECT

None

MACF

Multiple AC Fail

Major

AC

ACF

MAN

Manual Off

Minor

RECT

None

MFA

Multiple Rectifier Fail

Major

RECT

RFA

MMAN

Multiple MAN Alarm

Major

RECT

None

PHA

Phase Or Low Output

Minor

AC

None

RIC

Rectifier Incomplete Config

Warning

None

None

RFA

Rectifier Fail

Minor

RECT

RFA

Default Display
The default display shown in figure 4-8

provides basic system status. The controller

returns to this display after approximately three minutes after the last time a key is

pressed.

Figure 9-8:

Millennium II Controller Default Display

The first line shows:

# of Alarms

# of Warnings

Date

Time

The larger text in the middle of the screen shows:

Plant Voltage

Plant Load (Current)

Advertising