Galaxy Power System GPS2436

Issue 1 August 2012

91

All input and output connections comply with SELV requirements.

Insulation on field-wired conductors should be rated no less than 90° Celsius. Size

conductors based on listed recommendations. Wiring internal to enclosed

equipment cabinets should be rated at 105° Celsius (minimum).

Torque or secure electrical connections to the values specified on labels or in the

product documentation.

Alarm contacts on the office alarm connector are not fused within the controller;

therefore, current limiting protection for these contacts must be provided by

external circuits. Maximum ratings for alarm connections are 60Vdc and 0.5

amperes. Exceeding these maximum ratings could result in fire or damage to the

unit.

In enclosed equipment cabinets, the chassis must be connected directly to the

cabinet ac service ground bus. For applications in huts, vaults, and central offices,

the chassis must be connected to the system integrated ground grid.

This product operates equally well if installed as part of the Isolated Ground

Plane (Isolated Bonding Network) or the Integrated Ground Plane (Mesh-

Bonding Network, aka, Common Bonding Network). Lineage recognizes there are

different grounding techniques that are equally successful. Adhere to a

commonly accepted and consistent grounding approach to ensure personnel

safety, network protection, and proper equipment operation. Multiple low

impedance paths to Earth ground are essential.

The equipment and subassembly ports are suitable for connection to intra-

building or unexposed wiring or cabling. The equipment and subassembly ports

can be connected to shielded intra-building cabling grounded at both ends.