Galaxy Power System GPS2436

Issue 1 August 2012

80

signal again raising the plant voltage.

• The rectifier will shutdown and restart two additional

times.

• Upon the third shutdown, the rectifier’s ALM LED lights

and the rectifier’s display indicates “HO”.

• The controller receives the RFA signal from the rectifier

and initiates a restart signal 5-6 seconds later.

• The rectifier restarts again raising plant voltage.

• The rectifier shuts down and restarts 3 additional times.

• During these shutdowns the Green ON LED on the

rectifier blinks and the ALM LED on the rectifier is not lit.

• Upon the fourth shutdown, the rectifiers ALM LED lights

and the rectifier’s display indicates “HO”.

• Any external RFA office alarm has occurred.

• The controller will wait 5-6 minutes and issue one final

restart signal initiating the final sequence of shutdown

and restart events before the rectifier locks out, requiring

personnel intervention.

o

Prior to this occurring, change the value of the

system voltage to its original value. Press ENTER

to save the change.

o

Restart the rectifier from the front panel by using

the menus:

8.

Using the Float Settings Menu Screens, select Set Point.

9.

Use the Arrows, and UP/DOWN keys to change the system float voltage

setpoint to its original value

This value must be at least 0.5V below the HV alarm threshold setting.

Press ENTER to save.

10.

Controller Observations:

• The plant voltage returns to it’s original value

• Power Major alarm (PMJ) retires

• RECT and MAJ LEDs are extinguished

Rectifier Observations:

• Rectifier is operating normally