Galaxy Power System GPS2436

Issue 1 August 2012

87

Rectifier

Rectifier Specifications850022020 GPS2436 Prod Man r01.docx

Electrical

Input

Voltage Range

175-275Vac, 2-wire, single phase
(150 Vac - 300 Vac with reduced performance)

Frequency Range

45 - 66 Hz

Power Factor

> 0.98 at > 50% rated output

AC Surge Protection: It is important that ac surges reaching rectifiers do not exceed the capacity of the

rectifier internal surge protection. Protection must be provided external to the GPS system, if necessary,

to limit surge energy reaching the rectifiers. Site surge protection must be coordinated with rectifier

internal surge protection and must clamp at a lower voltage than the rectifier internal protection. The

internal protection voltage and current characteristics of the rectifiers are as follows:

Phase to Phase Voltage

MOV Conduction Current

320Vac (RMS)

0A

620V maximum clamping

1mA (DC test current)

810Vpeak

100A peak (8 x 20s)

Output All

High Voltage Shutdown

Internal Selective High Voltage Shutdown

(ISHVSD)



Backup High Voltage Shutdown (BUHVSD)

Float: 56.0Vdc Nom.

1,

2

Boost: 56.0Vdc Nom.

1,

2

Equalize:

59.52 ± 1Vdc Nom.

1,

2

Float/Boost: 59.52Vdc

3

Equalize: 66.0Vdc

3

1. Selectable/programmable through Galaxy Controller

2. Factory default settings – actual range is 44 - 60Vdc

3. Factory default settings – Float/Boost range is 58.51 - 60.53Vdc,

Equalize range is 65.2 - 67.0Vdc

Output NE100AC24ATEZ

Output Power

1

3,000W maximum

Output Current

1

55Adc maximum from -40°C to +65°C

42.5Adc at +75°C

30Adc at +85°C

Rectifier derates at approximately

1 ampere per degree C (+65°C to +85°C)

Float/Boost Voltage

21-29Vdc

Total Harmonic Distortion

<5% at full load

Regulation

±0.5%

Ripple

100 mVrms

Noise

< 2mV psophometric