Components – GE Industrial Solutions GPS2436 User Manual
Page 8
Galaxy Power System GPS2436
Issue 1 August 2012
8
Components
AC Input connects the commercial and/or standby ac power sources to the
rectifiers within the system and provides overcurrent protection. In some
applications the ac service is wired directly to the rectifiers and overcurrent
protection is provided at the service panel.
Rectifiers convert an ac source voltage into the dc voltage level required to
charge and float the batteries and to power the using equipment.
Controller provides the local and remote control, monitoring, and diagnostic
functions required to administer the power system.
Batteries provide energy storage for an uninterrupted power feed to the
using equipment during loss of ac input or rectifier failure.
DC Distribution Panel provides overcurrent protection, connection points for
the using equipment, and bus bars used to interconnect the rectifiers,
batteries, and dc distribution.
Battery Connection Panel provides connection points for the battery strings
through battery disconnect fuses or contactors and current monitoring
shunts.