Controller defaults, Dip switch settings – GE Industrial Solutions GPS2436 User Manual
Page 55
Galaxy Power System GPS2436
Issue 1 August 2012
55
Controller Defaults
Dip Switch Settings
The Millennium has 8 dip switch positions (SW202) that may be changed. SW202 is
located on the MCR1 board, above the MCR2 board. (See figure 4-7)
Figure 9-7:
Millennium II Controller Dip Switches
Table 9-G: Millennium II Controller Dip Switch Settings
Switch
Position
Default
Description
Closed
(1)
Open
(0)
SW202-8 1
Front Panel Configuration
ENABLED
DISABLED
SW202-7 0
Modem/Aux/Local/Gateway/USB/
IRDA Port Setting Configuration
(Remote Access)
ENABLED
DISABLED
SW202-6 0
Enhanced Security Mode (See
table 4-H, for features affected
ENABLED
DISABLED
SW202-5 1
Auxiliary Port Configuration
RS-232
RS-485
SW202-4 1
Remote Rectifier in Standby
ENABLED
DISABLED
SW202-3 0
Boost Mode
ENABLED
DISABLED
SW202-2 1
Reserved for Future Use
ENABLED
DISABLED
SW202-1 1
Reserved for Future Use
ENABLED
DISABLED