Controller Defaults

Dip Switch Settings
The Millennium has 8 dip switch positions (SW202) that may be changed. SW202 is

located on the MCR1 board, above the MCR2 board. (See figure 4-7)

Figure 9-7:

Millennium II Controller Dip Switches

Table 9-G: Millennium II Controller Dip Switch Settings

Switch

Position

Default

Description

Closed

(1)

Open

(0)

SW202-8 1

Front Panel Configuration

ENABLED

DISABLED

SW202-7 0

Modem/Aux/Local/Gateway/USB/

IRDA Port Setting Configuration

(Remote Access)

ENABLED

DISABLED

SW202-6 0

Enhanced Security Mode (See

table 4-H, for features affected

ENABLED

DISABLED

SW202-5 1

Auxiliary Port Configuration

RS-232

RS-485

SW202-4 1

Remote Rectifier in Standby

ENABLED

DISABLED

SW202-3 0

Boost Mode

ENABLED

DISABLED

SW202-2 1

Reserved for Future Use

ENABLED

DISABLED

SW202-1 1

Reserved for Future Use

ENABLED

DISABLED