High float voltage alarm – new installations – GE Industrial Solutions GPS2436 User Manual

Page 77

Advertising
background image

Galaxy Power System GPS2436

Issue 1 August 2012

77

connection points on the plant shunt(s).

2.

Calculate the plant load, in amperes, as measured by the DVM.

a) Divide the mV DVM reading by the rated shunt mV value

b) Multiply this result by the shunt ampere rating

This value is the plant load measured by the DVM, in amperes.

3.

Using the Meter Calibration Menus, reset the plant Plant Current

reading by selecting RESET LOAD. Press the Enter key to reset the Load.

This will remove any pre-existing user calibrated values if they exist.

4.

Wait at least 5 seconds and press the ESCAPE key.

5.

Select CALIBRATE LOAD. Use the Arrows, and UP/DOWN keys to

calibrate the system Load. Press ENTER to save.

NOTE:

The maximum total change is +/-10% of the cuurent load value.

6.

Press the <ESCAPE> key until the default screen is displayed. Verify that

the plant current reading has been changed.

NOTE:

This operation is performed and verified ONLY if plant load is constant

during the calibration procedure.

Observation:

• Displayed System load changes to new value.

High Float Voltage Alarm – New Installations

Step

Action for Testing the High Float Voltage Alarm

NOTE:

Clear all controller alarms for this test.

NOTE:

The high voltage alarm test is completed by raising the plant voltage

above the threshold set for HFV (High Float Voltage) .

NOTE:

Raising the plant voltage on a working system is left to the discretion of

the user.

• This test could disrupt power to working equipment.

• If the test is performed, verify that the plant is in FLOAT

mode

• Rectifier voltage has been set to the normal level after

completing the test.

1.

Using the Voltage Alarms Menu Screens, note High Float Alarm

threshold value. _________

2.

Using the Float Settings Menu Screens, select Set Point and note the

value. ________

NOTE:

The next step WILL RAISE the system voltage.

3.

Use the Arrows, and UP/DOWN keys to change the system float voltage

setpoint to 0.1V above the High Float Alarm Threshold.. Press ENTER to

save.

4.

Observe:

• The plant voltage increases to the set voltage

• Power Minor alarm (PMN) is generated

• RECT and MIN LEDs are illuminated