Thermal probes, Usb interface – GE Industrial Solutions GPS2436 User Manual

Page 44

Advertising
background image

Galaxy Power System GPS2436

Issue 1 August 2012

44

8.

After approximately 1 minute, the green LED on the front of the module will

blink once approximately every 5 seconds. Detailed troubleshooting

information may be found in the User’s Guide for Millennium II Controller

Advanced Features manual.

Thermal Probes

Without thermal probes, many of the controller’s battery management features will not

function, or produce erroneous results. Some features requiring thermal inputs are:

• Slope Thermal Compensation

• Reserve Time Prediction

• High Temperature Alarm

• Ambient High and Low Temperature Alarms

• High Temperature Disconnect

Step

Action

NOTE:

The controller supports a number of thermal probe inputs. The type of

probe used determines where it is connected on the controller. Detailed

thermal probe and battery management information may be found in the

User’s Guide for Millennium II Controller Advanced Features manual.

1.

The following table shows the type of probe and connector location on the

Millennium:

Type of Probe

Comcode

Controller Connection

Location

10/30K

P3

210E Thermal Probe

Mux

P3

1 Wire Temperature

Monitoring Devices

P7

Terminal Block

Interface for 3

additional 10k probes

or 210E connection

TB2

Pin

Description

1

Probe 2

2

Probe 2 RTN

3

Probe 3

4

Probe 3 RTN

5

Probe 4

6

Probe 4 RTN

USB Interface

This interface is reserved for future use.

Advertising