General specifications – GE Industrial Solutions Millennium II Controller J85501P-1 User Manual

Page 11

Advertising
background image

Basic Installation and User’s Guide for the Millennium II Controller

Issue 3 January 2008

11

General Specifications

Basic Millennium II specifications are summarized in table 2-B. Consult service center
for other details.

Table 2-B: General Millennium II Controller Specifications

General

Specifications

Input Voltage Range

±24 Vdc, -48 Vdc (Range: 18-60V)

Maximum Input Power

36W depending upon options

Operating Temperature Range

-40 to 75 °C (-40 to 167 °F)

Storage Temperature Range

-40 to 85 °C (-40 to 185 °F)

Physical Specifications

9.24 in. H, 20.76 in. W, 2.14 in. D

Display

8-line by 40-character backlit LCD

Cabinet Mounting Requirements

Door mounted

Input/Outputs

Specifications

Form C Alarm Output Contact Ratings

60VDC at 0.5A

Plant Voltage Measurement

Accuracy

0 to 50 °C (±.05% of full scale + 1

count)

-40 to 85 °C (±0.1% of full scale + 1

count)


Resolution



48V Systems: ±40 mV
24V Systems: ±25 mV
48V Systems: ±70 mV
24V Systems: ±40 mV
0.01V

Plant Current Measurement (Up to 2
shunts)

Accuracy

Resolution


0 to +50 °C : ±0.5% of full scale
-40 to +85 °C: ±1.25% of full scale
1A

Temperature Measurement

Accuracy

Thermistor temperature

One-Wire Serial probes


Resolution



-5 to +55 °C: ±2°C
-40 to +85 °C: ±3°C
-5 to +55 °C: ±1°C (next release)
-40 to +85 °C: ±3°C
0.1°C

4-20mA Input Monitor

Accuracy
Resolution


±100µA
±10.0µA

General (0-5V) Input

Accuracy


0 to +50 °C: ±0.5% of full scale