Basic Installation and User’s Guide for the Millennium II Controller

Issue 3 January 2008

70

Disconnect
Reconnect

7.

Slope Thermal Compensation

Slope thermal compensation information, if implemented in the system, should
be recorded, so that it can be programmed when the new controller has been
installed.

Record this information by selecting the following menus from the front panel
display: MENUÆ CONFIGÆ STC

STC Enabled/Disabled

Nominal Temperature

Step Temperature

Disconnect Temperature

Low Temperature

Upper Temperature

Raise Voltage Enable

Temperature Units

8.

Rectifier Float Setpoints


Rectifier float setpoint determines the system voltage.

Record the float setpoint by selecting the following menus from the front panel
display: MENU ÆCONFIGÆ RECT MANAGER

Plant V

I limit

SHVSD

9.

Securing Contactors

If Battery and Load contactors are in the system, contactor control boards
should be configured so that they do not OPEN during the controller
replacement. To ensure that these contactors do not open, force all LVLD and
LVBD contactors closed.
NOTE: These contactors may have already been forced closed per customer
requirements. If so, then proceed to the next step.

To force LVLD contactors closed, place SW300 in the up position as shown in
figure 6-2 and 6-3.