GE Industrial Solutions Millennium II Controller J85501P-1 User Manual

Page 42

Advertising
background image

Basic Installation and User’s Guide for the Millennium II Controller

Issue 3 January 2008

42

Symbol Default

Designation

Default
Severity

Default LED Default

Relay

ATB

Alarm Test Aborted

RO

None

None

ATF

Alarm Test Failed

Warning

None

None

BBL

Memory Backup Battery Low Warning

None

None

BCA

Battery Type Conflict

Warning

None

None

BDA Battery

on

Discharge

Major BD

BD

BFA

Battery Test Failed

Minor

BAT

None

BID

Bay Interface ID Conflict

Major

CTLR

CTLR

BTA

Battery Test Active

RO

BD

BD

BTJ

Battery Thermal Major

Major

BAT

None

BTN

Battery Thermal Minor

Minor

BAT

None

CCH Configuration

Changed

RO

None

None

CDFA

Converter Distribution Fuse

Major

RECT

MJF

CDID Converter

ID

Conflict

Major

RECT

None

CFA Converter

Fail

Minor RECT None

CLC Clock

Changed

RO

None None

CMA

Minor Communications Failure Minor

CTLR

None

CMFA

Multiple Converter Fail

Major

RECT

None

CNF1 Contactor

1

Failed

Major

BAT

None

CNF2 Contactor

2

Failed

Major

BAT

None

CNF3 Contactor

3

Failed

Major

BAT

None

CNO1 Contactor

1

Open

Major

BAT

None

CNO2 Contactor

2

Open

Major

BAT

None

CNO3 Contactor

3

Open

Major

BAT

None

COF Queue

Overflow

Warning None None

COR

Number Did Not Respond

Warning

None

None

CPA

Circuit Pack Fail

Major

CTLR

CTLR

CRA Controller

Fail

Major CTLR CTLR

DID Rectifier

ID

Conflict

Major RECT None

EMD

Energy Management Disabled Warning

None

None

EPD

Excess Plant Drain

Minor

RECT

None

EPO

Emergency Power Off

Critical

BATT

None

EPR

External Password Reset

Warning

None

None

ETO

Engine Transfer Timeout

Minor

AC

None

EXL

Excessive Login Attempts

Warning

None

None

FAJ

External Fuse Major

Major

DIST

MJF

FAN

External Fuse Minor

Minor

DIST

MNF

HCL History

Cleared

RO

None None

Advertising