USB Interface

This interface is reserved for future use.

Wiring Alarm Outputs

These external alarms may be wired to customer external office alarms at their

destination.

Form-C Alarm Contact Ratings

60Vdc, 0.3A

Conductor Size for terminating on Alarm
board

18 – 22AWG (if less than 18AWG, use
multi-conductor cable for mechanical
integrity)

Refer to Table 4-B and 4-C for lead designations and their descriptions for leads

terminating on the BSL alarm interface board.

Table 4-B: Controller Alarm Descriptions and Pin Numbers

Pin

Number

Signal

Name

Pin

Number

Signal

Name

Pin

Number

Signal Name

1 PCRAO 33

MJFR

65

FAN

2 PCRAC 34

MNFR

66 AMN

3 PCRAR 35

MNFC

67 TFLT

4 PCRVR 36

MNFO

68 TBST

5 PCRVC 37

BDO

69 TRTN

6 PCRVO 38

BDC

70 PBTR

7 PCREO 39

BDR

71

PBT

8 PCREC 40

ACFR

72

OS

9 PCRER 41

ACFC

73

TR1

10 PMJAR 42

ACFO

74

TEQ

11 PMJAC 43

RFAO

75

ETR

12 PMJAO 44

RFAC

76

ETRR

13 PMJEO 45

RFAR

77

RO

14 PMJEC 46

HVR

78

ROR

15 PMJER 47

HVC

79

TR2

16 PMJVR 48

HVO

80

TR4

17 PMJVC 49

UR1O

81 RBRPO

18 PMJVO 50

UR1C

82

TBD

now general

I/O-1