Basic Installation and User’s Guide for the Millennium II Controller

Issue 3 January 2008

68

Step Action

NOTE: Verify that the Alarm center has been notified of potential alarms being

generated.

1.

Place System in Float Mode

From the Default Display of the controller, note the system mode of operation:

IF the mode is FLOAT, go to Step 2.
If the mode is NOT Float (ex. – BOOST), place the system in FLOAT
mode before going to Step 2.

2.

Turn all Available Rectifiers On

If rectifiers have been manually turned off, turn them back on. Verify that all
rectifiers are on and sharing load.

3.

Noting the Dip Switch Settings


Dip Switch settings determine if some controller features are enabled or
disabled. If the Millennium II controller is to have the same configurations,
the old settings on SW202 must be noted:

Figure 6-1: Millennium Controller Dip Switch Positions


Record the Switch Positions for future reference –

Basic Controller (BSH) Dip Switch Settings

Switch

Position

Description Switch

Setting

(1 or 0)

SW202-8 Front

Panel

Configuration

SW202-7

Auto Rectifier Restarts

SW202-6

Critical = Major Relays

SW202-5 Alarm

Test

SW202-4

HVSD during Alarm Test

SW202-3 Boost

Mode

SW202-2 External

Timed

Boost

SW202-1

Password Reset for Indep Modem