Table 4-K: Rectifier Alarm Defaults

Symbol Default

Designation

Default
Severity

Default LED Default

Relay

ACF AC

Fail

Minor AC

ACF

CLM

Rectifier Current Limit

RO

None

None

ERD

Excess Rectifier Drain

Minor

RECT

None

ETS

External Transfer Shutdown

Minor

RECT

None

HPA Half

Power

Minor RECT None

LCA

Low Current Alarm

Minor

RECT

None

LSF Load

Share

Fuse

Minor RECT None

MACF

Multiple AC Fail

Major

AC

ACF

MAN Manual

Off

Minor RECT None

MFA

Multiple Rectifier Fail

Major

RECT

RFA

MMAN

Multiple MAN Alarm

Major

RECT

None

PHA

Phase Or Low Output

Minor

AC

None

RIC Rectifier

Incomplete

Config

Warning

None None

RFA Rectifier

Fail

Minor RECT RFA

Default Display
The default display shown in figure 4-8

provides basic system status. The controller

returns to this display after approximately three minutes after the last time a key is
pressed.

Figure 4-8:

Millennium II Controller Default Display

The first line shows:

# of Alarms

# of Warnings

Date

Time


The larger text in the middle of the screen shows:

Plant Voltage

Plant Load (Current)