Basic Installation and User’s Guide for the Millennium II Controller

Issue 3 January 2008

57

from this screen.

Contactor

1-3

Type

This setting identifies the type of contactor,
BATTERY, LOAD or NONE that has been
installed in the plant. Be sure that the wiring
for the contactor being configured matches
the type chosen here. For standard GPS
configurations using BIC cards, Contactor 1 is
wired to and controls all BATTERY
contactors in the plant. Contactors 2 and 3 are
wired to and control only LOAD contactors.
To toggle between the various contactor
types, move the cursor to one of the fields and
use the <+> or <-> key to select the desired
type. Press <ENTER> to save the change.

Disconnect

This setting configures the plant voltage at

which the contactor will disconnect from the

bus. Use the <+> or <-> key to adjust the

voltage to the desired level. Press <ENTER>

to save the change.

Reconnect

This setting configures the plant voltage at

which the contactor will reconnect to the bus.

To prevent the contactor from re-operating

when battery voltage increases due to load

removal, a voltage several volts higher than

the disconnect voltage is recommended. Use

the <+> or <-> key to adjust the voltage to the

desired level. Press <ENTER> to save the

change.