Basic Installation and User’s Guide for the Millennium II Controller

Issue 3 January 2008

88

5.

Write Statistics to File

If controller statistics are to be saved, then they must be written to a file.
NOTE: Millennium Controller Statistics CANNOT be loaded into the
Millennium II. They can only be printed, viewed and exported to other
programs.

Using a computer, connect to the Millennium either locally or remotely and
write the Statistics to a file.

NOTE: If using Easy View:

Once connected to the controller, select the
REPORTS Æ STATISTICS menu and proceed with saving
this information.

6.

Noting the Dip Switch Settings

Dip Switch settings determine if some controller features are enabled or
disabled. If the Millennium II controller is to have the same
configurations, the old settings must be noted:

(see Figure 6-8)


Record the Switch Positions for future reference –

Basic Controller (BSH) Dip Switch Settings

Switch

Position

Description Switch

Setting

(1 or 0)

SW202-8

Front Panel Configuration

SW202-7

Auto Rectifier Restarts

SW202-6

Critical = Major Relays

SW202-5 Alarm

Test

SW202-4

HVSD during Alarm Test

SW202-3 Boost

Mode

SW202-2

External Timed Boost

SW202-1

Password Reset for Indep Modem

IntelligentController (BSJ) Dip Switch Settings

Switch

Position

Description Switch

Setting

(1 or 0)

SW203-8

Remote Rectifier in Standby

SW203-7

Remote Rectifier Turn On

SW203-6

Full Access through Local Port

SW203-5

Full Access through Aux Port

SW203-4

Full Access through Modem Port

SW203-3

Modem/Local/Aux Setting Config

SW203-2

Local Port(Event Log or Terminal)

SW203-1

Aux Port(RS232 or RS485)

SW204(4-8) NOT

USED

SW204-3

Enhanced Remote Security

SW204-2

Remote Alarm Test

SW204-1

Rectifier Energy Management