GE Industrial Solutions Millennium II Controller J85501P-1 User Manual

Page 41

Advertising
background image

Basic Installation and User’s Guide for the Millennium II Controller

Issue 3 January 2008

41

Voltage Threshold Ranges and Default Values

Table 4-I: Voltage Threshold Ranges and Default Values

Low

High

Default

Very Low Voltage (VLV)

24V

20.00 25.50 23.00

48V

40.00 51.00 46.00

Battery on Discharge (BD)

24V

Float

23.00 28.00 25.00

24V

Boost

23.00 28.00 25.00

48V

Float

46.00 55.00 51.00

48V

Boost

46.00 55.00 51.00

High Float Voltage (HFV)

24V

Float

24.75 29.75 26.50

24V

Boost

25.75 31.75 26.50

48V

Float

50.00 60.00 53.00

48V

Boost

52.00 60.00 53.00

High Voltage Shutdown Alarm (HV)

24V

Float

24.75 29.75 26.8

24V

Boost

25.75 31.75 26.8

48V

Float

50.00 60.00 53.6

48V

Boost

52.00 60.00 53.6

Rectifier On Threshold (ROT)

24V

20.00 25.00 22.00

48V

40.00 51.00 44.00


Controller Alarm Severity, LED and Relay Default Values

Table 4-J:Controller Alarm Severity, LED and Relay Default Values

Symbol Default

Designation

Default
Severity

Default LED Default

Relay

AAC ACO

Active

RO

None

None

ABS

Alarm Battery Supply Fuse

Major

CTLR

CTLR

AMJ Auxiliary

Major

Major None None

AMN Auxiliary

Minor

Minor None

None

ATA

Alarm Test Active

RO

None

None