Basic Installation and User’s Guide for the Millennium II Controller

Issue 3 January 2008

78

Figure 6-7: Millennium Controller Switch Locations


Refer to the Switch Settings section in the Removal section.

Millennium Controller – Millennium II Dip Switch Settings Mapping

Millennium

Switch

Position

Description

Millennium II Setting

NOTE: Position 8 is the leftmost dip switch

SW202-8 Front

Panel

Configuration

Set SW202-8 to:

0 if Millennium was 0
1 if Millennium was 1

SW202-7 Auto

Rectifier

Restarts

Using the front panel, go to:

MenuÆConfigÆPlant

Config Auto Restart to:

Enabled if Millennium was 1
Disabled if Millennium was 0

SW202-6 Critical

=

Major

Relays

Using the front panel, go to:

MenuÆConfigÆSystem Settings

Config Crit=Major to:

Enabled if Millennium was 1
Disabled if Millennium was 0

SW202-5

Alarm Test

Using the front panel, go to:

MenuÆConfigÆAlarm Test

Config Test to:

Enabled if Millennium was 1
Disabled if Millennium was 0

SW202-4

HVSD during Alarm
Test

Using the front panel, go to:

MenuÆConfigÆAlarm Test

Config HV Shutdown to:

Enabled if Millennium was 1
Disabled if Millennium was 0

SW202-3

Boost Mode

Using the front panel, go to: