Basic Installation and User’s Guide for the Millennium II Controller

Issue 3 January 2008

64

rectifier shuts down.

• The Green ON LED on the rectifier blinks, the ALM LED

on the rectifier is not lit.

• After 5-6 seconds the rectifier initiates its own restart

signal again raising the plant voltage.

• The rectifier will shutdown and restart two additional

times.

• Upon the third shutdown, the rectifier’s ALM LED lights

and the rectifier’s display indicates “HO”.

• The controller receives the RFA signal from the rectifier

and initiates a restart signal 5-6 seconds later.

• The rectifier restarts again raising plant voltage.

• The rectifier shuts down and restarts 3 additional times.

• During these shutdowns the Green ON LED on the

rectifier blinks and the ALM LED on the rectifier is not
lit.

• Upon the fourth shutdown, the rectifiers ALM LED lights

and the rectifier’s display indicates “HO”.

• Any external RFA office alarm has occurred.

• The controller will wait 5-6 minutes and issue one final

restart signal initiating the final sequence of shutdown and
restart events before the rectifier locks out, requiring
personnel intervention.

o Prior to this occurring, change the value of the

system voltage to its original value. Press ENTER
to save the change.

o Restart the rectifier from the front panel by using

the menus:

8.

Using the Float Settings Menu Screens, select Set Point.

9.

Use the Arrows, and UP/DOWN keys to change the system float voltage
setpoint to it’s original value
This value must be at least 0.5V below the HV alarm threshold setting.
Press ENTER to save.

10. Controller

Observations:

• The plant voltage returns to it’s original value

• Power Major alarm (PMJ) retires