GE Industrial Solutions Millennium II Controller J85501P-1 User Manual

Page 99

Advertising
background image

Basic Installation and User’s Guide for the Millennium II Controller

Issue 3 January 2008

99

10.

Aux Port Connections

Step Action

a.

On the controller, locate TB1. It is located at the top
of the board. (see Figure 6-11)

b.

If NO wires terminated on P203 with the old
Millennium,
then proceed to the next item for
installation.
If a cable terminated on P203, with the old
Millennium,
install the wires according to the
table below:

TB1 on

Millennium

II

Wires from

Millennium

1 TX+
2 TX-
3 RX+
4 RX-


c.

If a cable terminated on P203 with the old
Millennium, it was most likely a Gateway interface
cable. With the Millennium II, since the Gateway is
integrated, there is no need to connect a cable to the
Aux port, which is a new RJ45 connector anyway.


11.

Hardware/Software Dip Switch Settings


Whereas the Millennium controller had 3 sets of dip switches, the Millennium II
only has one set. Some features which originally required enabling/disabling
through a dip switch, now require software enabling.

Refer to the Switch Settings section in the Removal section.

Millennium Controller – Millennium II Dip Switch Settings Mapping

Millennium

Switch

Position

Description

Millennium II Setting

SW202-8 Front

Panel

Configuration

Set SW202-8 to:

0 if Millennium was 0
1 if Millennium was 1

SW202-7 Auto

Rectifier

Restarts

Using the front panel, go to:

MenuÆConfigÆPlant