Basic Installation and User’s Guide for the Millennium II Controller

Issue 3 January 2008

15

3 Safety

Safety Statements

Please read and follow all safety instructions and warnings before installing, maintaining,
or repairing the Millennium II controller:

The CE Mark demonstrates compliance with the European Union Council

Directives for Low Voltage and EMC.

The Millennium II platform is Underwriters Laboratories (UL) recognized per

Subject Letter 1801, DC Power Distribution Centers for Telecommunications
Equipment.

Install only in restricted access areas (dedicated equipment rooms, equipment

closets, or the like) in accordance with articles 110-16, 110-17, and 110-18 of the
U.S. National Electric Code (NEC), ANSI/NFPA No. 70, and pursuant to
applicable local codes.

This equipment is to be used in controlled environments (an area where the

humidity is maintained at levels that cannot cause condensation on the equipment,
the contaminating dust is controlled, and the steady-state ambient temperature is
within the range specified).

This equipment has been evaluated for continuous use in ambient temperature from

-40°C to 75°C.

This equipment must not be installed over combustible surfaces.

For installations in the United States, Listed compression connectors are to be used

to terminate Listed field-wired conductors where required. For all installations,
the appropriate connector is to be applied only to the correct size conductor as
specified by the connector manufacturer, using only the connector manufacturer’s
recommended tooling or tooling approved for that connector.

If the proper connector for the country of installation is not provided, obtain

appropriate connectors and follow manufacturer’s and all local requirements for
proper connections. All national and local rules and regulations should be followed
when making field connections.

All input and output connections comply with SELV requirements.

Insulation on field-wired conductors should be rated no less than 90° Celsius. Wire

conductor size should be sized per electrical codes for 90° Celsius wire, and based
on the ampacity of the associated protection device. Wiring internal to enclosed
equipment cabinets should be rated at 105° Celsius (minimum).