GE Industrial Solutions Millennium II Controller J85501P-1 User Manual

Page 56

Advertising
background image

Basic Installation and User’s Guide for the Millennium II Controller

Issue 3 January 2008

56

cell battery voltage as a function of
temperature.

Enabled

Enables or Disables the Thermal
Compensation Feature. Move the cursor to the
field and use the <+> or <-> key to Enable or
Disable. Press <ENTER> to save the change.

High

Temp

Comp

This feature allows the system to compensate
for high temperatures.

Volt Step
Down

Battery step temperature can be set from 113-
185F. At this temperature, the system voltage
is reduced by 0.17 X # of cells/string.

High Comp
Limit

This sets the maximum temperature for which
thermal compensation is active.

Decrease

This sets the slope (mV/degC) for high
temperature compensation.

Nominal
Temp

This field set the temperature at which no
compensation is required. The system voltage
is at the setpoint float mode.

Low Temp Comp

This feature allows the system to compensate
for low temperatures.

Low T
Comp

This enables or disables the low temperature
compensation feature.

Low Comp
Limit

This sets the minimum temperature for which
thermal compensation is active.

Increase

This sets the slope (mV/degC) for low
temperature compensation.

8. Recharge

Current

Limit

This feature sets the total amount of current
that will be allowed to recharge the batteries.

Limit

The configuration of this field enables or
disables the feature.

Limit to

This programmable value sets the maximum
amount of recharge current (in Amps) that
will be allowed for recharging the batteries.
The range is from 10 – 1000A.

9.

Contactors

Up to three optional LVD devices can be
connected to a Millennium and configured

Advertising