Basic Installation and User’s Guide for the Millennium II Controller

Issue 3 January 2008

35

Fused Battery Supply

BSL-93, 94 ABS: Alarm Battery Supply

This is an alternate plant voltage source for user alarm systems. This power is fused with

a 1-1/3 ampere ABS fuse.

BSL-95,96 DG: Discharge Ground

Plant ground/return source for user alarm systems.

Fuses

Two Fuses, located on the MCR1 board, provide protection for the controller input power
and Alarm Battery Supply, used to power alarm panels or other devices requiring the
power system voltage at no more than 1.3A.

Figure 4-4: Millennium Controller Fuses


FUSE Description

Fuse

Size

F1

Controller Input Power 3A

F2

Alarm Battery Supply
(ABS)

1.3A

Front Panel Display

LCD
The primary local interface for the Millennium II is an eight-line LCD assembly mounted
to the front of the primary GPS cabinet door. This user interface is a panel that includes a
backlit LCD module, two sections of status LEDs, system voltage test jacks, and an array
of simple push-button controls. This controller supports multiple LCD display
assemblies. It is backwards compatible to both existing Millennium LCD assemblies L51
and L50

shown in Figure 4-5. It is also compatible with the enhanced L52

LCD display

assembly (see figure 4-6) specifically developed for the Millennium II. This new display