9. Remote Communications

The instructions provided in this chapter should enable the user to establish remote communications

with the CXC. The communications protocol supports a web interface. All CXC models can be set up,

monitored and tested with an Ethernet 10/100 Base-T either locally or remotely. Local connection is also

possible with a PPP serial data connection. The installation manual describes some standard scenarios.
NOTE

: A step by step connection wizard – provided to establish remote communications with the CXC –

is available via the Alpha website (www.alpha.ca). The wizard does not work in Windows Vista or Win-

dows 7.

9.1 Establishing a Network Connection via a Crossover Cable

Laptop
1. Connect the network crossover cable between the host computer (e.g. laptop) and the Cordex

controller.

2. In Windows®, select the Start menu, Control Panel, and then select Network Connections.
3. Right-click on the icon for the Local Area Connection (to be used by the laptop computer) and then

select Properties.

4. Make sure Internet Protocol (TCP/IP) is checked; highlight it and then select Properties.
5. Check the radio button beside Use the Following IP Address and enter or verify the following

information:
IP address:

10.10.10.202

Subnet mask:

255.255.255.0

6. Click OK to close each window opened thus far.

CXC LCD
7. Login to the CXC: First, tap on the home page icon at the bottom left corner of the LCD touch screen

and select

LOGIN

. Next, enter the password

1234

and tap on

ACCEPT

. Last, close the message

window (access granted to the controller).

8. On the main menu, scroll down and tap on

Communications

and then tap on

IP Address

(6.5).

9. Enter or verify the following information (uncheck

Obtain Automatically

if necessary):

IP address:

10.10.10.201 (factory default)

Subnet mask:

255.255.255.0

To change a number, tap on the numeric field to edit via the virtual numeric keypad, see Figure 6.

10. Select the

√ icon to accept the new setting and return to the previous menu.

11. Return to the MAIN MENU navigation screen and press the

OPTION

button to evoke the

SAVE/

LOGOUT

pop-up window.

12. Select

SAVE

to save the new settings. A pop-up window will appear to confirm the selection (select

the

X

icon).

13. Select the

OPTION

button again and choose

LOGOUT

.

14. Tap on the home page icon at the bottom left corner of the LCD touch screen and select

RESET

, see

Section 4.4. To confirm the reset, tap on

ACCEPT

and then

REBOOT NOW

.

15. In Windows®, once the CXC has rebooted, launch Internet Explorer® 8 or greater and enter the IP

address of the CXC (10.10.10.201) in the address bar. Under

Tools\Internet Options\Security

, add the

logon address of the CXC to the Trusted Sites.

16. If the connection was successful, the password prompt will appear. Enter your name in the USER

NAME field and the default PASSWORD (1234). Select

OK

to proceed to the language selection

window.