7 rectifiers (and converters) information, T (4.7.2), 1 inventory update – Alpha Technologies Cordex Controller Ver.3.1x User Manual

Page 26: 2 rectifier report (converter report similar)

Advertising
background image

0700015-J0 Rev B

24

4.7 Rectifiers (and Converters) Information

4.7.1 Inventory Update

This button enables the user to re-acquire all the attached modules to the CXC and verify the existence of

all connected modules.
Tapping this button updates the inventory and returns the user to the home page. A pop-up window ap-

pears over the home page to show a progress bar of the number of modules acquired during the update.

Tapping the X button clears the pop-up from the active area.
Inventory update must be done whenever a module is removed from the system. The system is polled

with respect to the following scenarios:
• Module has failed and is no longer able to communicate, or
• User has removed a module from the system.

4.7.2 Rectifier Report (Converter Report similar)

Tap the

Rectifier Report

button to generate a report of all acquired modules in the system.

A new operations window appears with a list of the rectifiers in the system. The first column lists the serial

numbers of the modules. The report then displays the current output (A) of each module (or toggle for %

of maximum output) and the number of active alarms. The right most column displays the number of set-

tings out of tolerance (OOT per web interface).

FL + TC

54.00V

250A

Inventory Update

Rectifier Report

Converter Report

Select operation here

Alarm Indication

Return to previous screen

Figure 16 — Update (inventory) and report selection screen

Figure 17 — Rectifier (or Converter) report screen

Rectifier (or Converter) Locate Feature

Once a module is selected, the (module)

LEDs flash briefly.

Select a module and then tap

View

Details

to produce a new window

with pull-down menus showing all of

the alarms and settings that are out of

tolerance

Report headings for serial number, current

display (% or A), number of alarms and set-

tings out of tolerance (OOT)

A value of ‘---‘ indicates Comms Lost

FL + TC

54.00V

250A

Return to previous screen

Tap the rectifier display area to

enter an operation window for

converter/rectifier updates and

reports.

Advertising