4.7.3 Basic Programming Example

For details of the settings in the RECTIFIERS\ CONFIGURE SETTINGS menu, see 6.3.2:

1. Use the navigation arrows to scroll to the item that is to be changed; e.g. FLOAT VOLTAGE.
2. Enter a new value using the CXC virtual numeric keypad, e.g., 54.00.
Download new settings to all connected rectifiers:
3. Click the check mark in the lower right hand corner to return to MAIN MENU navigation screen.
4. Press the OPTION button to evoke the SAVE/LOGOUT pop-up window.
5. Select SAVE to save the new settings or select LOGOUT to clear. A pop-up window appears to

confirm the selection.

4.8 Voltage Mode Status and Temp Comp Settings

The Mode Status displays the current mode of operation:
• Float (FL)
• Equalize (EQ)
• Boost (BST)
• Battery test (BT)
The mode and temperature compensation (TC) appear in the upper left corner. The time duration, until

the mode changes, may also appears in that active area.
Refer to sections 4.9 to 4.12 for a description of the voltage modes.

Mode Status

To change modes:

1. Tap the Mode Status active area to enter the mode selection screen.
2. In the screen that appears, tap the required mode button.
3. Tap the check mark button in the lower right corner to verify the selection and return to the previous

screen.

The icon for the new mode now displays in the upper left corner of the GUI.

Figure 18 — Mode selection screen

Mode (+Temp Comp) display 

Mode Selection buttons

Additional functions display

here; such as, countdowns and

status of battery runtime

Battery Voltage and Load Current display

Alarm Indication

Verify action and return

to previous screen

FL + TC

54.00V

250A

Battery Voltage Mode

Periodic Auto-EQ Disabled

Auto BT Disabled

FL

EQ

BT

BST