Page 41: N 6.3

Advertising
background image

39

0700015-J0 Rev B

6.2 Converters

This menu category consists of converter alarms and controls. Parameters can be set/accessed such as

output voltage, OVP, high/low voltage alarms, and start delay.
The converter defaults are based on the system voltage of either 24 or 48 VDC.
At present, the converter software does not support:
• Two types of converters simultaneously
• 12, 125, and 220 VDC systems.
Other features include:

Active voltage control

Inventory update

Converter locate

Loadsharing

Firmware upgrade

Major and minor alarms

6.2.1 Converter Report

This feature provides the user with a list report (see 4.7.2, Figure 17) of all acquired converters in the

system. The first column lists the serial numbers of the converters. The report then displays the output

current of each converter under the Amps column (or toggle for % of maximum output) and the number

of active alarms under the Alarms column (if that converter is issuing an alarm). The right most column

displays the number of settings out of tolerance.
Select a converter and tap View Details to produce another list showing details of the entire converter

alarms and settings that are out of tolerance.

6.2.2 Configure Settings

This feature allows the user to configure settings (via menu items) for all of the acquired converters in the

system; such as:

Output Voltage

Start Delay

OVP

Enable CL Alarm

Input Voltage Shutdown

Input Voltage Restart

6.3 Rectifiers

This menu category consists of rectifier alarms and controls. Parameters can be set/accessed such as

float/equalize voltages, high/low voltage alarms, and start delay.

6.3.1 Rectifier Report

This feature provides a list report (see 4.7.2, Figure 17), of all acquired rectifiers in the system. The first

column lists the serial numbers of the rectifiers. The report then displays the output current of each recti-

fier under the Amps column (or toggle for % of maximum output) and the number of active alarms under

the Alarms column (if that rectifier is issuing an alarm). The right most column displays the number of

settings out of tolerance (OOT per web interface).
Select a rectifier and tap

View Details

to produce another list showing details of the entire rectifier alarms

and settings that are out of tolerance.

6.3.2 Configure Settings

This feature allows the user to configure settings (via menu items) for all of the acquired rectifiers in the

system.